Want to create an interactive transcript for this episode?
Podcast: HVAC School - For Techs, By Techs
Episode: Blends and Midpoint w/ Jim Bergmann
Description: Jim talks about dew point, bubble point, and midpoint in refrigerant blends. He also covers the purpose of each and why MeasureQuick displays midpoint on the gauges. We've formerly used mostly pure refrigerants. However, as new refrigerant blends come on the scene, we have to deal with glide, which indicates that we have a range of boiling temperatures instead of a fixed boiling point. We have bubble point and dew point, which are when the refrigerant starts to boil and finishes boiling, respectively; you generally use dew point to determine the superheat and bubble point to determine...