Want to create an interactive transcript for this episode?
Podcast: HVAC School - For Techs, By Techs
Episode: Check The Charge Without Connecting Gauges - Part 2
Description: In this second part of the podcast, Jim Bergmann wraps up the steps to check a system charge without connecting a gauge manifold. You can check the charge without gauges if you use the following process (and know your DTD, CTOA, etc.): Take the dry-bulb temperature. (Let's say it's 70°F in this example.) Subtract the DTD (35°F). Add target superheat (10°F). Check the suction line. It should be 45°F in this example. If your probe senses a temperature that is NOT within 5°F of the temperature you calculated, check the filter, evaporator coil, etc., for dirt. If th...